10 O/M's Mimic Circuits
When programmed as Yes" the output
modules mimic circuit activations. When
programmed as ”No" output modules give
circuit alarm indication. (Default = Yes)
11 Do Battery Test
When programmed as "Yes" the control panel
battery and any monitored PSU batteries are
tested every hour and when exiting the
engineer's mode. When programmed as "No"
the control panel battery and any monitored
PSU batteries are not tested. (Default = No)
12 F.Exit is Night
When programmed as “Yes" final exit circuits
change tonightcircuitswhenthesystemispart
set. When programmed as ”No" final exit
circuits remain as final exit circuits when the
system is part set. (Default = No)
13 Audible Time Switch
When programmed as Yes" the internal
sounder will activate when any of the time
switched outputs are active. When
programmed as No" the time switched
outputs remain silent. (Default = No)
14 Show Part Set Information (LED Keypads)
When programmed as “Yes" the display will
alternatebetweenshowingthetimeandwards
that are set when the system is part set. When
programmed as ”No" the display will always
show the time when the system is part set.
(Default = Yes)
15 Deferred Set
When programmed as “Yes" any night circuit
triggered during exit will restart the exit timer.
When programmed as ”No" any night circuit
triggered during exit will not reset the exit timer.
(Default = No)
16 Set with AC Off
When programmed as “Yes the system can
be set with no mains power. When
programmed as “No” the system cannot be
set with no mains power. (Default = Yes)
17 Loud Chime Tones
When programmed as “Yes” the chime tones
are always at full volume. When programmed
as “No” the chime tones are at the level set by
VR1 on the main PCB. (Default = No)
18 Invert Output 1
When programmed as “Yes” panel output 1 is
normal. When programmed as “No” panel
output 1 is inverted. (Default = No)
19 Invert Digi Outputs
When programmed as Yes" the eight
digicom outputs on the control panel switch
from 0V to +12V when active (+ve applied).
When programmed as “No” the eight digicom
outputs on the control panel switch from +12V
to 0V when active (+ve removed). (Default =
No)
20 On-Line Keypad
When programmed as Yes" the Menvier
Lineload On-Line Keypad feature is enabled.
When programmed as No the Menvier
Lineload On-Line Keypad feature is disabled.
(Default = Yes)
21 Restore Point ID
When programmedas "Yes"the PointIDrestore
status is transmitted. When programmed as
"No" point ID restore is not transmitted. (Default
= Yes)
22 User Authorised
When programmed as Yes the Menvier
Lineload software can only write information to
the control panel after the user has authorised
remote communications. When programmed
as“No”theMenvierLineloadsoftwarecanwrite
information to the control panel without user
authorisation. (Default = No)
23 Mimic Alarms and Faults
When programmed as Yes any outputs
programmed as the type "Circuit Alarm" will
activate when the relevant circuit is in alarm or
in a fault condition. When programmed as
“No” any outputs programmed as the type
"Circuit Alarm" will activate when the relevant
circuit is in alarm. (Default = No)
Engineer's Menu 1 TS900 Installation Manual
32