Remote Reset Algorithm
When the system is programmed for “Engineer
Reset” the requirement to send an engineer to site
can be overridden by the user by using the
“Remote Reset” facility. If an alarm is generated
the system will respond with a four digit “seed”
codewhichtheuserquotestotheAlarmReceiving
Centre or alarm company. The “seed” code is
then entered into a decoder and a unique
“Remote Reset” code is generated. This is passed
back to the user and on entering the “Remote
Reset” code, the system is reset.
The “Remote Reset” code is generated using an
algorithm identified by a 3 digit number.
Alternative algorithms can be selected but these
must correspond tothatusedby theARC(or alarm
company) otherwise the “Remote Reset” code will
be incorrect. (Default = 004)
Configuration
The configuration options are as follows:
00 Bell Is an SAB
When programmed as “Yes” the control panel
bell output applies 0V when active. When
programmed as “No” the control panel bell
output removes 0V when active. (Default =
Yes)
01 User 1 Limited
When programmed as “Yes” user 1 is disabled
from options 6 and 8 in user menu 2 , and all
options in user menu 3. When programmed as
“No” user 1 has access to all user menus and
options. (Default = No)
02 Fire Signals all
When programmed as Yes fire alarm
activationsaresignalled totheARCatalltimes.
When programmed as No fire alarm
activations are signalled to the ARC only when
the system is full set. (Default = No)
03 Silent 24hr Circuits
When programmed as “Yes 24hr circuit are
silent. When programmed as “No 24hr circuits
are audible. (Default = No)
04 Enable Duress
When programmed as “Yes” the reversalof the
first two digits on any passcode will generate a
duress alarm. When programmed as “No” the
reversal of the first two digits on any passcode
will NOT generate a duress alarm. (Default =
Yes)
05 Invert Abort O/P
When programmed as “Yes” the abort output
is normally active and deactivates for 5
seconds when an alarm is aborted. When
programmed as No the abort output is
normally inactive and activates for 5 seconds
when an alarm is aborted. (Default = No)
06 Set with Line Fault
When programmed as “Yes the system can
be set with a telephone line fault, however the
user will be asked to confirm this at the time of
setting. When programmedas “No”the system
can not be set with a telephone line fault.
(Default = Yes)
07 User Reset
When programmed as “Yes" alarms can be
reset by the user. When programmed as ”No"
alarms can onlybereset by theengineer orvia
remote reset. (Default = Yes)
08 Constant Exit Tones
When programmed as “Yes" exit tones remain
constant during exit. When programmed as
”No" exit tones rise in pitch during exit. (Default
= Yes)
09 High Security Engineer
When programmedas“Yes"theengineermust
enter his passcode and remote reset number
to gain access to engineer's menu 1. When
programmed as No" only the engineer's
passcode is required to access engineer's
menu 1. (Default = No)
Remote Reset
Algorithm > 004
Remote Reset
Algorithm > 010
Engineers menu 1
Select Option :-
Algorithm No.
8
Enter new No.
e.g. 010
ENT
StarburstLCD
LED
E1-
ENGR 1 -
004
004
010
010
Remote Reset Algorithm Flowchart
TS900 Installation Manual Engineer's Menu 1
31