Expansion Devices
There are several options for expanding the system:
TS700 LEC
The Local Expansion Card (LEC) provides two
programmable detection circuits and one
programmableswitched-veoutput.Upto5TS700LECs
can be connected on any one network.
TS900 NODE
The TS900 NODE provides eight programmable
detection circuits and two programmable outputs
(one switched +ve and one switched -ve). Up to 5
TS900NODEscanbeconnectedonanyonenetwork.
XNODE
The XNODE provides eight programmable detection
circuits,twoprogrammableoutputs(oneswitched+ve
and one switched -ve) and a loudspeaker output for
driving a 16 Ohm loudspeaker. Each XNODE can also
driveup to4remotekeypads. Up to16XNODEscan be
connected on any one network.
LEC8
The TSLEC8 Local Expansion Card (LEC) is designed to
be fitted inside the control panel it provides 8
programmable detection circuits. The control panel
will accept two LEC8s.
ID NODE
The ID NODE can be used as an alternative to the
standard TS900 NODE. It provides a single ID Detector
Loop for connection to 30 ID devices and 8
programmable outputs. Several options allow it to be
used on its own or with existing TS900 NODEs.
Other Devices
Printer
A DATAC printer or any standard RS232 printer can be
connected to the control panel to obtain system and
log print-outs.
CPA6.OM Output Module
Each output module provides eight switched -ve
outputs, the output modules can be daisy-chained
together to provide multiples of eight outputs. The
outputs can be used to indicate ward status
information and/or circuit alarm/mimic indications.
DC54/58/58M Digicom and Digi-modem
A 4-channel DC54 or 8-channel DC58 digital
communicatorcanbepluggedontothecontrolpanel
to allow alarm status information to be transferred to a
dedicated Alarm Receiving Centre. The 8 channel
DC58M digi-modem can be pluggedonto the control
panel, which functionsas a digital communicator and
V21 modem. The modem facility is required when
using the up/down loading feature.
NIB Networker Interface Board
A driver and receiver board that allows NODEs or
remotes to be driven up to 1 Km.
Technical Specifications
Control Panel
Part No: TS2500
Input Supply: 230V ± 10% 50Hz
Current: 220mA (normal)
300mA (alarm) with speaker
Power Supply: 1.5A
Standby Battery: 2 x 7.0Ah or 1 x 17Ah
Zones 2 to 1040
Panel Outputs: 1 = voltage free changeover
2 = Switched -ve @500mA
3 = Switched +ve @500mA
4 = Switched +ve @500mA
Digi Outputs 1-8: +ve removed
Source 5mA in 12V condition
Sink 100mA in 0V condition
Speaker Output: 16 Ohms
Bell Trigger: Switched -ve @500mA
Strobe Trigger: Switched -ve @500mA
Dimensions: 384(W) x 312(H) x 95(D) mm
Material: 1.2mm mild steel
Weight: 4.9 Kg
Environment: -10° to 55°C
LCD Remote Keypad
Part No: NETLCD
Display: 32 Character Liquid Crystal
Current: 50mA (normal) 60mA (alarm)
Zones: 2
Output: Switched -ve @100mA
Dimensions: 150(W) x 104(H) x 30(D) mm
Material: 3mm Polycarbonate
Weight: 282g
Environment: -10° to 55°C
Starburst Remote Keypad
Part No: NETSTAR
Display: 8 Character Liquid Crystal
Current: 50mA (normal) 60mA (alarm)
Zones: 2
Output: Switched -ve @100mA
Dimensions: 150(W) x 104(H) x 30(D) mm
Material: 3mm Polycarbonate
Weight: 263g
Environment: -10° to 55°C
TS2500 4of26 496513 Issue A