2
Settling Time 0-199 sec Whensettin g the system by"FinalExit"or "ExitTerminator", detectorsthatare
on the exitroute sometimes take3- 4 secondsto settle after activation. The
delay programmed in this timer is used to allow these detectors to sett le
before the system or area is set.
3
Digicom Delay 0-199 sec When the system is part-set the communication of an alarm s ignal t o the
central station may be delayed by the value set in this timer.
4
Exit Time 0-199 sec This timer sets the delay between the user initiating the ex itprocedure and
the system (orarea)actuallySetting.Ifdu ringtheexittimea n ExitTerminator
circuit is activated the exit time is cancelled and the system sets
immediately.
5
Entry Time 0-199 sec The time allowed for entering the protected premises via the entry route
when the system is (Part) Set . Th e time is allocated to two entry periods. A
warning is given if thef irstis exceeded andafullalarmoccursifthesecond
is exceeded .
6
Bell Durati on 0-199 min The duration time of the bell and sounders when an alarm occurs.
7
Bell Delay 0-199 min This timer delays the activati on of the bell output and interna l sounders.
8
Double Knock 0-199 sec This is the Double Knock time window in which either:
Two circuit activation must occur within this time to generate an alarm
condition. Or the ci rcuit must remain active for the whole duration of this
time to generate an alarm condition. This will only apply to circuits with the
Double Knock attribute
9
Test Time 0-30 days This timervaries thenumberofdays that Testattributemay beapplied to a
circuit. If the time is set to 000 then circuitswillremain on test until the "Test"
attribute is removed.
Ta ble 5b. System Timers
Setting Modes
The system may be set by one of the following modes:
Final Exit - The system or area will set when the "Final Exit" circuit is activated and after
the "Settle Ti me" has expired.
Exit Terminator - The system or area will set when the "Final Exit" circuit is activated, the "Exit
Terminator" button is pressed and after the "Settle Time" has expired.
Timed Exit - The system or area will set when the "Exit Tim e" has expired or if the "Exit
Terminator" button is pressed.
The se tting mode for full-set, part-set groups A, B and C are programmed as follows:
1. Ensure that "Engineer Menu 1 " is selected .
2. Press 6 to select the Setting Modes option.
3. The display will show: S.BY-
4. Select setting group by pressing:
0 fo r full-set
A fo r part-set group A
B fo r part-set group B
C fo r part-set group C
5. The display will show the current setting mode.
20
Programming TS700 Installation Manual
S.BY-
Ent er setting group 0,A,B or C.
F-FE
Ent er setting mode 1,2,3 or 0.